DLM — Electronics, Tools & Home Store

Categories

Categories currently unavailable.

Open catalog
Language
UAEN
Wireless smoke, heat and carbon monoxide detector FireProtect 2 RB (Heat/Smoke/CO) white
4 399 ₴
In Stock
1

Wireless smoke, heat and carbon monoxide detector FireProtect 2 RB (Heat/Smoke/CO) white

SKU FireProtect 2 RB (30295)

Description

Detection accuracy through steam, dust, and time

FireProtect 2 is a next-generation device for instant fire detection. The unique smoke chamber requires no regular cleaning, the dual-spectrum sensor distinguishes smoke from steam, the thermistor quickly responds to the combustion of synthetic materials, and smart software algorithms minimize false alarms. All of this complies with modern fire safety standards. Thanks to thoughtful industrial design, mounting, and in-app configuration, the detector is installed quickly and easily.

Operating principle
Smoke detection

FireProtect 2 detects smoke and ignores water vapor thanks to a bi-spectral optical sensor with blue and infrared LEDs. The LEDs emit light at different wavelengths, enabling the sensor to determine volatile particle size and react only to smoke.
The smoke chamber is protected against dust, dirt, and insects. Even if dust settles inside the smoke path, it does not impede or degrade detection. The optical system is designed so that non-volatile particles or insects cannot simultaneously enter both light beams and trigger a false alarm.

Rapid temperature rise detection

Two built-in thermistors are responsible for detecting temperature rise. The thermistors are located externally on the detector body for faster threat detection.
If the ambient room temperature exceeds 64°C or rises at a rate of 10°C per minute or faster, the detector recognizes this as a rapid temperature rise and triggers an alarm. A temperature alarm can trigger even if there is no smoke in the room.

Hazardous carbon monoxide concentration detection

FireProtect 2 detects hazardous carbon monoxide levels via a built-in chemical sensor with an operating life of at least 10 years.
Carbon monoxide (CO) is a colorless, tasteless, and odorless gas generated by incomplete combustion of fuel in vehicle engines and heating appliances running on coal or other types of natural fuel. For example, it can originate from fireplaces, boilers, or heating systems. In sealed or poorly ventilated spaces, life-threatening concentrations of carbon monoxide can accumulate.

Interconnected fire alarms

The detector supports interconnected fire alarms. This function activates the built-in sirens of all Ajax fire detectors in the system when at least one of them triggers. In case of fire, this alerts as many occupants as possible across the facility.
FireProtect 2 detectors feature an enhanced interconnected alarm algorithm that activates all fire detector sirens within 20 seconds. This feature works when detectors operate with an Ajax hub.

Autonomous operation without a hub

FireProtect 2 detectors can be used standalone without connecting to an Ajax hub. In this scenario, the detector alerts to fire alarms using its built-in siren and LED indication, but does not send notifications to the user's smartphone, Ajax Translator, or PRO Desktop.

Manual and automatic self-testing

FireProtect 2 periodically checks the status of batteries and sensors. If a fault is detected, the hub immediately notifies users and the central monitoring station, while the detector activates the corresponding optical and acoustic alert via its siren and LEDs. All device states can be inspected at any time in Ajax apps.
The detector supports a test mode activated by pressing the front panel. The front panel features a mechanical button, allowing it to be pressed by hand or with a handle. The test triggers the built-in siren and runs sensor diagnostics, allowing the installation engineer to verify functionality at any time and demonstrate the multi-tone sound and light patterns for various alarm types to the client.

Jeweller communication technology

Jeweller is a radio protocol for fast, reliable two-way communication between the hub and connected devices. The protocol provides a wireless range with FireProtect 2 of up to 1700 meters, allowing installation across very large facilities.
Jeweller handles event and alarm transmission. It also coordinates the interconnected alarm trigger within 20 seconds across a system with any number of FireProtect 2 detectors. Jeweller ensures users and central monitoring stations receive live status telemetry in Ajax apps.

Fast mounting and pairing

FireProtect 2 requires no housing disassembly for installation. The replaceable or non-replaceable batteries come pre-installed, and the SmartBracket mounting plate detaches tool-free. The SmartBracket panel has a 90° freedom of rotation, allowing the installer to align the detector precisely after mounting.
Pairing with the Ajax security system takes less than a minute: open the Ajax app, scan the QR code, and assign the device to a room and security group.


Manufacturer
Ajax
Brand
Ajax
Detector type
Wireless
Sensor type
Combined detector
Model
FireProtect 2 RB (Heat/Smoke/CO)
Control panel connection method
Wireless
Wireless signal range
1700 m
Detected gases
CO
Compatibility
Hub Plus, Hub 2 (2G), Hub 2 (4G), Hub 2 Plus, Hub Hybrid (2G), Hub Hybrid (4G), ReX, ReX 2
Communication
Jeweller communication technology
Proprietary wireless technology for alarm and event transmission.
Features:
- Two-way communication.
- Device spoofing prevention.
- Block encryption with floating key.
- Instant notifications.
- Remote configuration via Ajax apps.

Radio frequency bands
868.0 – 868.6 MHz

Maximum Effective Radiated Power (ERP)
Up to 20 mW
Automatic power control to reduce power consumption and radio interference.

Radio signal modulation
GFSK

Radio communication range
Up to 1700 m
Between detector and hub (or radio signal range extender) in open space.

Radio communication encryption
All transmitted and stored data protected by block encryption with floating key.

Frequency hopping
To prevent radio interference and jamming.
Sensing elements
Smoke sensor, Temperature sensor, CO (carbon monoxide) sensor
Smoke detection
Sensing element
Optical dual-spectrum sensor
Distinguishes smoke by airborne particle size.

False alarm protection
Ignores water vapor.

Patented smoke chamber
Protects smoke sensor from dust, dirt, and insects.
Hazardous temperature detection
Sensing element
Compliant with Class A1 temperature detector standards
Requirements of EN 54-5 and BS 5446-2 standards.

High temperature threshold alarm
At temperatures above 64°C

Rapid temperature rise alarm
When temperature rises more than 10°C in 1 minute (or faster)
Carbon monoxide (CO) detection
Sensing element
Chemical CO sensor
Alarm upon exceeding accumulated CO dosage
>50 ppm (0.005%) – in no more than 90 minutes
>100 ppm (0.01%) – in no more than 40 minutes
>300 ppm (0.03%) – in no more than 3 minutes

A concentration of 400 ppm (0.04%) for 3 hours can be life-threatening. The detector stops warning of hazardous CO levels once the concentration drops below 50 ppm (0.005%) within 1 minute.

Sensor lifespan
10 years
The detector must be replaced after 10 years of operation.
Anti-sabotage protection
Tamper switch against opening
Alerts when attempting to tear the detector from the surface or detach it from the mounting panel.

Protection against spoofing
Device authentication

Communication loss detection
Within 15 minutes
Detection time depends on the configured number of unacknowledged data packets (set in Jeweller or Jeweller/Fibra settings). Fixed polling interval: 300 seconds.
Additional features
Built-in siren
85 dB volume at a distance of 3 meters
Audible alarm notification. Active until the trigger condition clears or silenced by the user.

Interconnected fire alarms
All fire detectors in the system trigger built-in sirens once any single detector detects an alarm. Interconnected alarm activates within one hub-detector polling period, but no later than 20 seconds.

LED indication
Green - Power indication
LED on device body blinks every 56 seconds. Compliant with EN 50291.
Yellow – Fault indication
LED on device body lights up when faults are detected, such as low battery, contaminated smoke chamber, or end of life.
Red - Fire alarm indication
LED on device body illuminates when the detector signals a fire alarm.

Button on the detector front panel
In standby mode, pressing runs smoke chamber self-test. During an alarm or fault, pressing mutes the audible alert.
Operating temperature range
0 °C - +50 °C
Operating humidity
Up to 80%
Ingress protection class
IP20
Power supply
2 x CR123A
Dimensions
123.7 × 123.7 × 44.7 mm
Weight
TBC g
Color
White

Specifications

Model
Wireless smoke, heat and carbon monoxide detector FireProtect 2 RB (Heat/Smoke/CO) white
SKU
FireProtect 2 RB (30295)
Modification
Wireless smoke, heat and carbon monoxide detector FireProtect 2 RB (Heat/Smoke/CO) white
Condition
New (Original factory package)
Warranty
Official manufacturer warranty

Delivery & Payment

Nova Poshta delivery across Ukraine

Dispatch to post branches, parcel lockers, or by courier to your doorstep. All packages are insured for 100% of value. Delivery time: 1–3 business days.

Payment & Pick-up

Flexible options: Cash on delivery at Nova Poshta branch or bank transfer invoice (IBAN) for individuals, FOP and companies.

Shopping Cart

0 items

Your cart is empty

Add items from the catalog to place an order.

Explore Catalog