Detection accuracy through steam, dust, and time
FireProtect 2 is a next-generation device for instant fire detection. Its unique smoke chamber requires no routine cleaning, a dual-spectrum sensor distinguishes smoke from steam, a thermistor responds quickly to synthetic material combustion, and intelligent software algorithms minimize false alarms. Compliant with modern fire safety standards. Designed for quick, hassle-free installation and in-app configuration.
Operating Principle
Smoke Detection
FireProtect 2 detects smoke while remaining immune to water vapor thanks to a bi-spectral optical sensor equipped with blue and infrared LEDs. The LEDs emit light at different wavelengths, enabling the sensor to determine volatile particle sizes and trigger solely on smoke particles.
The smoke chamber is protected against dust, debris, and insects. Any dust accumulation will not impair detection reliability. The optical chamber geometry ensures insects or non-volatile particles cannot intercept both light beams simultaneously to cause false alarms.
Rapid Temperature Rise Detection
Two built-in thermistors detect temperature increases. Thermistors are positioned externally on the enclosure for faster hazard detection.
If room temperature exceeds 64°C or rises at a rate exceeding 10°C per minute, the detector identifies this as a rapid temperature rise and initiates an alarm. Heat alarms trigger regardless of smoke presence.
Dangerous Carbon Monoxide Concentration Detection
An integrated chemical CO sensor with a service life of at least 10 years monitors dangerous carbon monoxide levels.
Carbon monoxide (CO) is a colorless, odorless, and tasteless gas produced by incomplete combustion in vehicle engines, fireplaces, boilers, or fuel-burning appliances. Poorly ventilated enclosed spaces can quickly accumulate lethal concentrations.
Interconnected Fire Alarm
The detector supports interconnected fire alarms. This function triggers built-in sirens across all Ajax fire detectors in the system when any single unit activates, alerting everyone across the facility.
FireProtect 2 uses an optimized interconnected alarm algorithm activating all fire sirens within 20 seconds. This feature requires hub connectivity.
Standalone Operation Without Hub
FireProtect 2 detectors can be operated autonomously without connecting to an Ajax hub. In this mode, the detector sounds alarms via built-in siren and LED indicators, but does not transmit push notifications to smartphones, Ajax Translator, or PRO Desktop.
Manual and Automated Testing
FireProtect 2 constantly runs self-diagnostics on battery and sensor status. Any malfunction triggers instant notifications to users and monitoring centers, while the device indicates faults via sound and LED signals. System status can be viewed in the Ajax app at any time.
Manual test mode is triggered by pressing the front panel, which integrates a mechanical button easily pressed by hand or with an extension tool. The test cycle runs the siren and sensor checks, allowing installers to verify device performance and demonstrate alarm modes.
Jeweller Radio Communication Technology
Jeweller is a proprietary two-way radio protocol providing secure communication between the hub and connected devices with a range of up to 1,700 meters. The range allows coverage across very large facilities.
Jeweller transmits alarms and events, synchronizing interconnected sirens in under 20 seconds. It also keeps device telemetry updated in the Ajax app.
Fast Mounting and Setup
FireProtect 2 requires no housing disassembly during installation. Replaceable or sealed batteries come pre-installed, and the SmartBracket mounting plate detaches without tools. The bracket offers a 90° rotation freedom to align the detector after mounting.
Connecting to an Ajax security system takes under a minute by scanning the QR code in the Ajax app.
Manufacturer
Ajax
Brand
Ajax
Sensor type
Wireless
Detector category
Combined detector
Model
FireProtect 2 RB (Heat/Smoke/CO)
Connection to FACP
Wireless
Wireless range
1700 m
Detected gases
CO
Compatibility
Hub Plus, Hub 2 (2G), Hub 2 (4G), Hub 2 Plus, Hub Hybrid (2G), Hub Hybrid (4G), ReX, ReX 2
Communication
Jeweller communication technology
Proprietary wireless protocol for alarms and events.
Features:
- Two-way communication.
- Device spoofing prevention.
- Block encryption with floating key.
- Instant notifications.
- Remote configuration via Ajax app.
Radio frequency bands
868.0 – 868.6 MHz
Maximum Effective Radiated Power (ERP)
up to 20 mW
Automatic power control to reduce power consumption and radio interference.
Modulation
GFSK
Radio communication range
up to 1700 m
Between detector and hub (or range extender) in line-of-sight.
Data encryption
All transmitted and stored data protected by block encryption with floating key.
Frequency hopping
To prevent radio interference and jamming.
Sensing elements
Smoke sensor, Heat sensor, CO (carbon monoxide) sensor
Smoke detection
Sensing element
Dual-spectrum optical sensor
Distinguishes smoke by airborne particle size.
False alarm immunity
Immune to water vapor.
Patented smoke chamber
Protects smoke sensor from dust, dirt, and insects.
Heat detection
Sensing element
Class A1 temperature sensor requirements
Compliant with EN 54-5 and BS 5446-2 standards.
High temperature alarm
at temperatures above 64°C
Rate-of-rise temperature alarm
when temperature rises by more than 10°C in 1 minute (or faster)
Carbon monoxide (CO) detection
Sensing element
Chemical CO sensor
Accumulated CO dose alarm thresholds
>50 ppm (0.005%) – in under 90 minutes
>100 ppm (0.01%) – in under 40 minutes
>300 ppm (0.03%) – in under 3 minutes
A concentration of 400 ppm (0.04%) for 3 hours is life-threatening. The detector clears the warning when concentration drops below 50 ppm (0.005%) within 1 minute.
Sensor lifespan
10 years
The detector must be replaced after 10 years of operation.
Tamper protection
Tamper switch
Alerts on attempts to detach detector from surface or remove mounting bracket.
Anti-spoofing
Device authentication
Connection loss detection
within 15 minutes
Loss detection time depends on polling intervals and packet settings (configured in Jeweller settings). Fixed polling interval: 300 seconds.
Additional features
Built-in siren
85 dB volume at 3 meters distance
Acoustic alarm active until cause is cleared or silenced by user.
Interconnected fire alarm
System fire detectors activate onboard sirens simultaneously upon detection by any unit within one polling cycle (max 20 s).
LED Indication
Green - Power indication
Flashes once every 56 seconds in compliance with EN 50291.
Yellow - Fault indication
Flashes upon detecting faults (low battery, contaminated chamber, end-of-life).
Red - Fire alarm indication
Flashes when a fire condition is detected.
Front panel button
In normal mode: initiates smoke chamber self-test. During alarm/fault: mutes acoustic alert.
Operating temperature range
0 °C - +50 °C
Operating humidity
up to 80%
Protection class
IP20
Power supply
2 x CR123A
Dimensions
123.7 × 123.7 × 44.7 mm
Weight
TBC g
Color
Black